Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL00716
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL00716 DENIED 4/13/05

1. Specify the voltage, phase, and amperage rating, and fault current rating of the new panel. Indicate MCB or MLO. If the intent is to refeed the existing owner's loads from the new panel, specify this. If existing circuits have to be extended/or re-routed, specify this.
2. Please demonstrate that the available fault current at the existing panels will not exceed their rating. In other cases where services have been updated but where the original panels were retained, City DSD has allowed this providing that the new disconnect had a current limiting overcurrent protective device. Willing to discuss.
3. Service conductors total 1500 MCM. Per NEC 250.102 (C) and Table 8, 1500(0.125) = 187.5 MCM. Next size larger is 4/4. Specify the Main Bonding Jumper to be 4/0.

APPLICANT SHALL GO TO PIMA COUNTY ADDRESSING AND OBTAIN DESIGNATIONS FOR ALL APARTMENTS. ALL UNITS SHALL BE ATTACHED TO THIS PERMIT. INCLUDES ONE OWNER'S PANEL AND EIGHT APARTMENTS. AFTER PIMA COUNTY ADDRESSING, APPLICANT SHALL GO TO CUSTOMER SERVICE REPRESENTATIVES TO HAVE UNITS ATTACHED TO PERMIT.