Permit Number - T05EL00501
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL00501 DENIED 3/15/05

1. Provide scaled site plan with plotted locations of all new and existing equipment.
2. Provide fault current rating of all new equipment.
3. Provide fault current rating of existing sub-panel.
4. Provide fault calculations as necessary to demonstrate that all new and existing equipment is rated for the AFC.
5. The #4 GND between the service enclosure and the disconnects consists of a redundant path to ground, and shall be removed.