03/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL00480 DENIED 3/11/05
1. SES is at 200A, but is feeding 1000A distribution section, and is anticipated to carry 1725A load. Please clarify.
2. (7) (500) MCM = 3500 (0.125) = 437.5, minimum size Main Bonding Jumper. Please add this requirement to the plans.
3. Please provide for the bonding together of both new and existing Grounding Electrode Systems.