| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL00480 DENIED 3/11/05 1. SES is at 200A, but is feeding 1000A distribution section, and is anticipated to carry 1725A load. Please clarify. 2. (7) (500) MCM = 3500 (0.125) = 437.5, minimum size Main Bonding Jumper. Please add this requirement to the plans. 3. Please provide for the bonding together of both new and existing Grounding Electrode Systems. |