Permit Number: T05EL00391
Parcel: 105102420

Address:
455 E WETMORE RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL00391
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL00391 DENIED 2/28/05

1. Minimum font size is 10 point, which is a little over 1/8".
2. Provide disconnects for new refrigeration equipment per NEC 422 Part III.
3. Put X'FMR TLR on Panel HB schedule. It appears that X'FMR TR on this panel was intended to be TLR.