Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL00391
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL00391 DENIED 2/28/05 1. Minimum font size is 10 point, which is a little over 1/8". 2. Provide disconnects for new refrigeration equipment per NEC 422 Part III. 3. Put X'FMR TLR on Panel HB schedule. It appears that X'FMR TR on this panel was intended to be TLR. |