Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL00316
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL00316 DENIED 2/16/05 1. Provide Panel and Circuit number for all circuits. 2. Provide location of panel on plans. 3. Provide panel schedule and load calculations. 4. Provide disconnect per NEC 600.6. 5. Provide sufficient information about the transformer to allow Plans Examiner to evaluate compliance with NEC 066.23. |