Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05EL00182
Parcel: 118080340

Review Status: Stopped

Review Details: ELECTRICAL

Permit Number - T05EL00182
Review Name: ELECTRICAL
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2005 ANY ENGINEERING REVIEW Stopped
01/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL00182 DENIED 1/27/05
1. Document electrical loads, ie., (4) (500) W lighting fixtures.
2. Document conductor size and type from GFI to lights.
3. Document voltage, amperage rating, phase, and available fault current rating of service equipment.
4. Provide TEP Available Fault Current.
5. Provide sizing of Grounding Electrode conductor per NEC 250.66.
10/17/2005 DSTARK1 ZONING REVIEW Stop