Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2005 ANY ENGINEERING REVIEW Stopped
01/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL00182 DENIED 1/27/05
1. Document electrical loads, ie., (4) (500) W lighting fixtures.
2. Document conductor size and type from GFI to lights.
3. Document voltage, amperage rating, phase, and available fault current rating of service equipment.
4. Provide TEP Available Fault Current.
5. Provide sizing of Grounding Electrode conductor per NEC 250.66.