Permit Review Detail
Review Status: Stopped
Review Details: ELECTRICAL
Permit Number - T05EL00182
Review Name: ELECTRICAL
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2005 | ANY | ENGINEERING | REVIEW | Stopped | |
| 01/27/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL00182 DENIED 1/27/05 1. Document electrical loads, ie., (4) (500) W lighting fixtures. 2. Document conductor size and type from GFI to lights. 3. Document voltage, amperage rating, phase, and available fault current rating of service equipment. 4. Provide TEP Available Fault Current. 5. Provide sizing of Grounding Electrode conductor per NEC 250.66. |