Permit Number: T05EL00177
Parcel: 14042046E

Address:
6608 S TUCSON BL

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL00177
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL00177 DENIED 1/26/05
1. Put project address on all sheets.
2. Indicate that method of neon installation as specified on applies to east elevation as well as north elevation.
3. Provide power requirements for equipment. Voltage, phase, and watts or amps.
4. Provide panel and circuit number for all neon circuits.
5. Provide panel schedule and load calculations.
6. Provide a disconnect per NEC 600.6.
7. Specify conductor and conduit size and type.
8. Demonstrate that lighting systems comply with NEC 600.9 (D).
9. Demonstrate that transformers comply with NEC 690.21 (C).
10. Demonstrate that the transformer is identified and listed for its use. NEC 600.23 (A).
11. Demonstrate that the transformer is in compliance with NEC 600.23 (B).
12. Demonstrate that the transformer complies with NEC 600.23 (C), (D), & (E).
13. Demonstrate compliance with NEC 600.41 (A).