Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL00177
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL00177 DENIED 1/26/05 1. Put project address on all sheets. 2. Indicate that method of neon installation as specified on applies to east elevation as well as north elevation. 3. Provide power requirements for equipment. Voltage, phase, and watts or amps. 4. Provide panel and circuit number for all neon circuits. 5. Provide panel schedule and load calculations. 6. Provide a disconnect per NEC 600.6. 7. Specify conductor and conduit size and type. 8. Demonstrate that lighting systems comply with NEC 600.9 (D). 9. Demonstrate that transformers comply with NEC 690.21 (C). 10. Demonstrate that the transformer is identified and listed for its use. NEC 600.23 (A). 11. Demonstrate that the transformer is in compliance with NEC 600.23 (B). 12. Demonstrate that the transformer complies with NEC 600.23 (C), (D), & (E). 13. Demonstrate compliance with NEC 600.41 (A). |
| 01/26/2005 | PATRICIA GEHLEN | ZONING | REVIEW | Approved |