Permit Number: T05CM06495
Parcel: 116161350

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM06495
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2006 GERRY KOZIOL WWM REVIEW Denied needs wastewater 8th floor review. fronts 30" public sewer
02/10/2006 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied February 3, 2006 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T05CM06495
LP2A Job No. 2060161.006

City of Tucson
201 N. Stone Ave. 1st Floor
Tucson, AZ 85701

Re: Plan Review: Anita SFR #1
Address: 929 N. Anita Ave

Linhart Petersen Powers Associates (LP2A), a Bureau Veritas Company, has completed a review of the following documents on behalf of the City of Tucson:

1. Plans: Two (2) sets of plans (8 sheets, 1 through 8) with cover sheet not dated or stamped.

2. Truss Calculations: None provided.

Structural Calculations: None provided.

Energy Compliance: One (1) set of MECcheck Compliance Report.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

LINHART PETERSEN POWERS ASSOCIATES
A Bureau Veritas Company




Randy McCoy, Senior Plans Examiner
ICC Plans Examiner


RM:pc c:/tucson\2060161.006pc1
enclosures




Re: Stories: One
Fire Sprinklers: No
Building Area (sq. ft.): 1,200(livable)

A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).


ARCHITECTURAL COMMENTS:

Headers must be within the span limitation of IRC table R502.1 (1). Refer to sliding glass door header. Sheet 4.

Note and specify all roof slopes. Sheet 4. IRC Chapter 9

Detail, note and size all roof drains/scappers. Sheet 4&5. IRC 903.4


MECHANICAL, ELECTRICAL AND PLUMBING COMMENTS:

Provide an exhaust fan to the outside from the laundry closet. Sheet 6. IRC 303

Please provide exhaust fans on mechanical plan. Sheet 7. IRC 303.

Provide a 4 inch diameter moisture exhaust vent for clothes dryer. Sheet 7. IRC M1501

Note and specify that at least one 20 amp branch circuits shall be installed to serve the laundry room, and this circuit shall serve no other outlets. Sheet 6. IRC E 3603.3.

Note and specify that two or more 20 amp small appliance circuits shall be provided to serve the kitchen, breakfast room and dining room. Such circuits shall serve no other outlets. Sheet 6. IRC E 3603.2 and E 3801.3.1

Provide smoke alarms in each sleeping room. Sheet 6. IRC 313

Please note that the panel circuit designation does not correspond with floor plan. Please revise. Sheet 6. IRC 106.

Provide bonding to the interior water piping. Sheet 6. IRC E 3509.6

Plumbing notes specify a natural gas, water heater, but plan specifies an electric water heater. Please clarify. Sheet 8. IRC 106


Provide drainage pipe isometric showing all drain, waste and vent piping. Sheet 8. IRC 106

Indicate the location of the temperature-pressure relief line from the water heater to the exterior of the building. Sheet 8. IRC P 2803.6.1

If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980 between 8:00 A.M. to 5:00 P.M., M-F.
02/15/2006 RBABBIT1 LANDFILL REVIEW Approved
02/22/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: February 22, 2006
ACTIVITY NUMBER: T06OT00194 / T05CM06495
PROJECT NAME: Arizona Acquisitions and Development
PROJECT ADDRESS: 929 West Anita Ave #1
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, FLOODPLAIN USE PERMIT APPLICATION


1. Add a general note to the site plan, sheet 1 stating the entire property is in FEMA Flood Hazard AO1 Flood Zone FIRM Panel #04019C 2226K. DS 2-02.2.1.A.15.

2. Show existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. DS 2-02.2.1.A.23.

3. Add a general note to the site plan, sheet 1 stating the finish floor elevation of each home is required to be a minimum of 2' above the highest existing natural grade.

4. Indicate the datum used for the finish floor elevation.

5. Provide fill quantities in cubic yards on the site plan.

6. Sign the floodplain use permit application, the signature line is located in the back of the application. The applicant or the applicant's authorized representative can sign the application.

7. Be advised once construction is complete, a condition of this permit contains a requirement that the applicant, or the applicant's authorized representative, complete a FEMA Elevation Certificate and is returned to the Development Services Department (DSD) Engineering Division prior to approval of final inspection. The original elevation certificate must be returned to the DSD Engineering Division.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2006 GBONILL1 OUT TO CUSTOMER Completed
02/24/2006 SUE REEVES REJECT SHELF Completed