Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM06482
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2006 | JMORALE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/11/2006 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 01/11/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/11/2006 | JMORALE1 | ENGINEERING | REVIEW | Needs Review | |
| 01/11/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t05cm06482. 01/11/06 1. Show the location of New Panel A, and service, on scaled drawings. 2. Indicate fault current at service, and provide fault calculations for New Panel A. Verify that the 22K rating is sufficient for AFC. |
| 01/11/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |