01/25/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 1/24/06
ACTIVITY NUMBER: T06CM06481
PROJECT NAME: STE 140
PROJECT ADDRESS: 4544 E. CAMP LOWELL
ARCHITECT / ENGINEER: RICK BRIGHT

PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Justify / clarify door into unoccupied suite 140 from exiting suite 110.
2) Justify restroom fixture count for occupant loads of all tenant spaces since the facilities are shared.
3) It appears restrooms are not accessible per ANSI 2003 A117.1 - see water closet clear floor space requirements.
4) Clarify tempered glazing in waiting area per section 2406.2.
01/26/2006 SUZANNE BOHNET ENGINEERING REVIEW Passed
01/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved