Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM06481
Parcel: 110055580

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM06481
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 1/24/06
ACTIVITY NUMBER: T06CM06481
PROJECT NAME: STE 140
PROJECT ADDRESS: 4544 E. CAMP LOWELL
ARCHITECT / ENGINEER: RICK BRIGHT

PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Justify / clarify door into unoccupied suite 140 from exiting suite 110.
2) Justify restroom fixture count for occupant loads of all tenant spaces since the facilities are shared.
3) It appears restrooms are not accessible per ANSI 2003 A117.1 - see water closet clear floor space requirements.
4) Clarify tempered glazing in waiting area per section 2406.2.
01/26/2006 SUZANNE BOHNET ENGINEERING REVIEW Passed
01/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2006 DELMA ROBEY OUT TO CUSTOMER Completed
02/01/2006 SUE REEVES REJECT SHELF Completed