Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM06417
Parcel: 140122210

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06417
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2005 JIM EGAN FIRE REVIEW Approved
12/27/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The 2003 UPC as adopted by the City of Tucson, effective 12/01/05.
2. Revise the location of the expansion tank so that no valves are between the water heater and the expansion tank.
3. Provide structural calculations and construction details for the water heater platform along with mounting instructions.
12/27/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/27/2005 GERRY KOZIOL WWM REVIEW Approved
12/27/2005 HEATHER THRALL ZONING REVIEW Approved
12/27/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2003 International Mechanical Code was adopted by the City of Tucson effective 12/01.05.
2. Provide a sequence of operation for the restroom exhaust fans to show that no recirculation of the supply air will occur.
3. Clarify the numbering of the rooftop units as shown on sheet M2.1.
4. The minimum insulation for the ductwork is R5 in unconditioned spaces.
5. Provide the exhaust flowrates for EF-1 and EF-2.
12/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM06417 12/27/05

1. Provide service load calculations, to include all occupancies on this service. An alternative approach may be to demonstrate that there was no load change, or that there was a net load decrease, considering demolition. In any case, please address circuit loadng: for example, the circuit which includes the receptacles in Office 102 does not appear to have a panel/ckt association; the lighting fixture and fan in 106 does not have a panel/ckt association; circuits 13,15, & 17 appear undercounted; tallys in Phases A & C of Panel A appear undercounted, not even considering the above. Please re-check all circuits and correct all which may apply.
2. Please comply with the 2003 IECC for lighting power budget. Reference Section 101.2.2.4.
12/27/2005 ROBERT SHERRY WATER REVIEW Approved
12/27/2005 SUZANNE BOHNET ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2006 BETH GRANT OUT TO CUSTOMER Completed