Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM06363
Parcel: 137270990

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM06363
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2007 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens FOR: David Rivera
Lead Planner Principal Planner

PROJECT:T05CM06363
1430 W. Valencia Rd.
Midvale Medical - Dental Plaza
Site Plan

Transmittal date:4th Review 3/23/07

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. DS 2-02.2.1.5 Clearly indicate all property lines by a heavier line weight with dimensions and bearings.

The copy of the lot combination covenant provided is not complete. Provide on the document the Case # T05CM06363 and then record the document. Provide on the site plan the recordation information for the covenant (docket and page).

2. DS 2-02.2.1.11 Provide a copy of the cross access agreement with the property to the west. Provide on the site plan the docket and page recordation information for the cross access agreement.

3. DS 2-02.2.1.12 Clearly indicate the location of all truncated domes for all handicap ramps which access vehicular use areas. The truncated domes indicated on details 7 and 8 of SP-2 are not in the correct locations. A 24" deep strip across the entire width of the access ramp or landing located on the ramp or landing abutting the pavement is required. Se ANSI 117.1-2003 Sec. 406.12 and 406.13.

A handicap parking sign is required for each handicap parking space. Clearly indicate locations of all signs.

On detail 3 on SP-2 indicate the minimum distance from grade to the bottom of the handicap sign is seven (7) feet, per City of Tucson standards.

On details 4 and 5 on SP-2 clearly indicate the maximum slope of the handicap parking spaces and access aisles. Per ANSI 117.1-2003 505.2 the maximum slope is 1:48.

4. Depending on changes to this plan and responses to comments, additional comments may be forth coming.


If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.
03/23/2007 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments
03/29/2007 ANDREW CONNOR LANDSCAPE REVIEW Approved
05/20/2007 SUNRISE ENGINEERING ENGINEERING REVIEW Denied May 17, 2007


City of Tucson
201 N. Stone Ave.
Tucson, Arizona 85726


RE: Plan Review: Midvale Medical Dental Plaza
Address: 1430 W Valencia Rd.


Sunrise Engineering’s Civil Engineering Plan Review Team has completed the 5th review of the following documents on behalf of the City of Tucson Development Services Department:

1. Plans: Three (3) copies (11 sheets) with cover sheet dated March 1, 2007.

These documents were reviewed only for their conformance to the City of Tucson Development Standards (Revised January 6, 2000). The previous comments were not responded to in letter, per the multiple requests. In particular, the roof drains appear to be on the sheets, but are not called out and there are no flow arrows to indicate how the roof will drain or slope. I have attached a list of all of the previous reviews and comments. Please respond in writing to each comment by marking the attached comment list or creating a response letter.

At this time we do not recommend approval. If you have any questions regarding the comments, please contact the reviewer Stephanie Schramm at 520-723-8634, between 8:00 A.M. and 5:00 P.M., Monday through Friday.


Sincerely,
SUNRISE ENGINEERING, Civil Engineering Plan Review Team




Stephanie Schramm, P.E.
Project Manager



The following items must be revised or added to the site plan. Please include a response
letter with the next submittal that states how all comments have been addressed.

RE-SUBMITTAL REQUIRED: SITE PLAN

01/12/2006 LOREN MAKUS ENGINEERING Denied
Comments:
The site plan must be approved before the building plan can be approved.
Show how roof drainage will be directed under adjacent sidewalks.

01/12/2006 LOREN MAKUS ENGINEERING Denied
Comments:
January 13, 2006
TO: Rio West Development and Construction
SUBJECT: Site Plan and Building Plans
REVIEWER: Loren Makus
ACTIVITY NUMBER: T05CM06363
SUMMARY: The Site Plan was reviewed by Development Services Department,
Engineering
Division on January 13, 2006. The Site Plan was not approved at this time. Please
address the following comments.
1. Show roof drainage patterns. Show that roof drainage will be routed under
sidewalks.
This should be made clear on the site plan as well as within the building plans.
2. Show maneuverability for the solid waste service vehicles from the street to the
solid waste enclosure location. This must include the adjacent property since access
to the solid waste container requires use of the adjacent parcel. The container
locations do not appear to be accessible once the parking area is in full use. Provide
recordation information for the cross-access easement.
3. The plat for this project area indicates that there is a flowage easement on this
property. Clearly show or describe this easement on the site plan.
4. Clearly identify the property lines for the the lots as shown on the plat for this
project. Expect comments from the zoning review section concerning the
combination of the lots that may be required.
5. The aerial photographs of the site do not appear to match the existing conditions
shown on the plan. Clarify the location of the existing and future right-of-way and
show the existing and future right-of-way conditions on the site plan.
Revise the Site Plan and submit two copies for review. Include a letter explaining
how each comment has been addressed. If you have any questions or if you wish to
discuss any of these comments, I can be reached at 520.791-5550 ext 1161 or by email at
loren.makus@tucsonaz.gov.
Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services

07/03/2006 LOREN MAKUS ENGINEERING Denied
Comments:
The previous comments have not been addressed. Address the previous comments
and re-submit.
Include a detailed response letter describing in detail how each comment has been
addressed.

02/09/2007 LOREN MAKUS ENGINEERING Denied
Comments:
The previous comments have not been addressed. Address the previous comments
and re-submit.
Include a detailed response letter describing in detail how each comment has been
addressed.

04/09/2007 LOREN MAKUS ENGINEERING Denied
Comments:
The following review comments are based on a building plan review. The building
plan
can not be approved prior to site plan approval. Please submit the city approved
site plan with the building plan set. The approved site plan will have City of Tucson
Fire, Zoning and Engineering stamps on this plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/30/2007 THAUSER1 OUT TO CUSTOMER Completed