| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/05/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide cleanouts in the existing private sewage collection system at a maximum interval of 100 feet per Section 719.1, UPC 2003. |
| 12/05/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The submitted energy code calculations call for the exterior walls of the building to be furred out and insulated with R-11 fiberglass insulation. The drawings do not appear to include furred out and insulated exterior walls. As drawn, the building does not meet the requirements of ASHRAE/IESNA 90.1-2001. Reference Section 701.1, IECC 2003. |
| 12/06/2006 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
| 12/06/2006 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 12/06/2006 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |