Permit Number: T05CM06363
Parcel: 137270990

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM06363
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2006 DAVE MANN FIRE REVIEW Approved
12/05/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide cleanouts in the existing private sewage collection system at a maximum interval of 100 feet per Section 719.1, UPC 2003.
12/05/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The submitted energy code calculations call for the exterior walls of the building to be furred out and insulated with R-11 fiberglass insulation. The drawings do not appear to include furred out and insulated exterior walls. As drawn, the building does not meet the requirements of ASHRAE/IESNA 90.1-2001. Reference Section 701.1, IECC 2003.
12/06/2006 DROBEY1 ENGINEERING REVIEW Needs Review
12/06/2006 DROBEY1 ZONING REVIEW Needs Review
12/06/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2006 DELMA ROBEY APPROVAL SHELF Completed
12/06/2006 DELMA ROBEY OUT TO CUSTOMER Completed
12/06/2006 DELMA ROBEY REJECT SHELF Completed