Permit Number: T05CM06355
Parcel: 11005527A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06355
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2006 JMORALE1 ENGINEERING REVIEW Needs Review
01/03/2006 JMORALE1 WWM REVIEW Needs Review
01/03/2006 JMORALE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review T05CM06355 12/22/05

1. Provide a disconnect for the new Water Heater. Reference NEC 422 Part III.
2. WH is 4 KW on electrical panel schedule, but is 2 KW per Sheet P-1. Please clarify, and specify voltage requirements on the Plumbing Schedule.
3. Heat Pump has 3-phase power on the electrical panel schedule, but Equipment Schedule Sheet M-1 specifies single phase power. Coordinate with Mechanical and clarify.
4. Show location of building service entrance on scaled drawing. Note that Site Plan, Sheet SP-1, was not included in review submittal, thus Electrical Plans Examiner can not back-check location of service transformer.
5. The 2003 IECC allows 1.1 W/SF for office spaces, not 1.6.
6. The new panel feeder, #4, only has ampacity of 85A, and as such is not protected by a 100 AF.
01/03/2006 JMORALE1 WATER REVIEW Needs Review
01/03/2006 JMORALE1 ZONING REVIEW Needs Review
12/21/2005 JIM EGAN FIRE REVIEW Denied Submit site plan showing location of property lines.
12/22/2005 DAVE MANN PLUMBING-COMMERCIAL REVIEW Approved
12/22/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide approved site plan show property lines and accessible path into building.
2) Office #5 needs key note #1 for safety glass.
3)Clarify in breakroom work surface meets accessibility requirements per section 902.1
12/22/2005 DAVE MANN MECHANICAL-COMMERCIAL REVIEW Approved