Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM06350
Parcel: 13506136C

Address:
2560 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06350
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM06350 .. 2560 S KOLB ROAD .. WALGREEN'S CANOPY .. DGL .. 1ST REVIEW .. 1/11/06 ..

S1. Provide Site Plan by Architect of Record showing Property lines for the site and the location of the work dimensionally located from two adjacent property lines and adjacent structures.
S2. Provide Completed code review checklist by Architect of Record.
S3. Provide drawings and documents with a minimum font size of 1/8" for review and record purposes, ref S1.0 and S2.0.
S4. Utilize current Code designations on drawings, ref T1.0.
S5. The Type of Construction is limited to a single Type of Construction for a Building, if more than one Type of Construction exists show required Fire Walls and Hourly fire-rating of these Walls on the drawings.
S6. Separate permits required for signs.
S7. Provide specifications for architectural materials of construction ref A1.0, including :
1. Built-up membrane roofing.
2. E.I.F.S.
3. Fasteners.
4. Flashing.
S8. Provide architectural details, including :
1. Splicing of built-up membrane roof (new to existing).
2. Canopy facia to existing wall.
S9. Provide addressing per Pima County Addressing Ordinance.
S10. Structural review and comments will take place when readable drawings are submitted, see comment S3 above.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
12/21/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/21/2005 JIM EGAN FIRE REVIEW Approved
12/21/2005 GERRY KOZIOL WWM REVIEW Passed
12/21/2005 HEATHER THRALL ZONING REVIEW Approved
12/21/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/21/2005 LOREN MAKUS ENGINEERING REVIEW Approved
12/21/2005 ROBERT SHERRY WATER REVIEW Approved
12/29/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Provide circuit and panel designation. 2.Provide panel load calculations with circuit loads 3.Indicate overcurrent protection 4.Indicate fixture,lamps wattages etc. 5.Provide the existing service loads and the size of the existing service lateral conductors.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2006 DELMA ROBEY OUT TO CUSTOMER Completed
02/03/2006 SUE REEVES REJECT SHELF Completed