Permit Number: T05CM06345
Parcel: 107120870

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM06345
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2007 MARTIN BROWN FIRE REVIEW Denied Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.

Smoke detectors are also required in units.
03/29/2007 STEVE SHIELDS ZONING HC SITE REVIEW Approved
03/30/2007 STEVE SHIELDS ZONING REVIEW Approved
04/02/2007 ANDREW CONNOR NPPO REVIEW Denied Submit Application for Exception; include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants.
04/02/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. A street landscape border, per Sec. 3.7.2.4 of the LUC, is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site except for points of ingress-egress. Access to refuse enclosure cannot be located within areas designated for landscaping, revise plan as necessary.

2. Refuse containers are to be placed so that the collection vehicle does not have to back into moving traffic, on or off the premises" per DS 6-01.4.1.I. Relocate refuse enclosure as necessary.

3. Submit Application for Exception; include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants.

4. Include with re-submittal approval documentation. Indicate on the lower right hand corner of the site plan, the variance and / or DSMR case number, date of approval, and any conditions imposed.

5. Additional comments may apply.
04/10/2007 JOSE ORTIZ ENGINEERING REVIEW Denied To: CLIENT: Mr. Ornelas
DATE: April 10, 2007
FROM: Jose E. Ortiz, PE
Engineering Division


SUBJECT: Street Address
Site plan T05CM06345 (Fourth Review)
T13S, R13E, Section 36

RESUBMITTAL REQUIRED: Site Plan


Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.

The following comments were not addressed. Revise the site plan to reflect proper responses to the following comments.

2. Additional spot grades are still needed to ensure positive drainage, and to clearly demonstrate that no nuisance ponding will occur on-site or on adjacent sites due to this proposed project. See the attached redlines for recommended locations of the additional spot grades.
3. If needed call out curb openings in PAAL/parking area to ensure proper drainage into water harvesting locations.
4. The plans do not meet D.S. 6-01.4.1.I which states that "Containers are to be placed so that the collection vehicle does not have to back into moving traffic, on or off the premises. A Development Service Modification Request (DSMR) will be required. The letter from John Clark will be taken into consideration during the DSMR process.

Comments are minimal therefore DSD Engineering will allow an over the counter approval once the above comments have been satisfied.

If you have any questions, I can be reached at 791-4259 ext. 305 Jose.Ortiz@tucsonaz.gov


Jose E. Ortiz
Civil Engineer
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-4259 ext. 76730 office

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2007 SUE REEVES OUT TO CUSTOMER Completed