Permit Number: T05CM06345
Parcel: 107120870

Review Status: Completed

Review Details: SITE

Permit Number - T05CM06345
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2006 JIM EGAN FIRE REVIEW Denied Fire spriklers required per 2003 IBC and IFC Sec. 903.2.7.
Provide fire sprinkler system design criteria on plans.
01/18/2006 JOSE ORTIZ ENGINEERING REVIEW Denied To: CLIENT: Mr. Ornelas
DATE: January 20, 2006
FROM: Jose E. Ortiz, PE
Engineering Division


SUBJECT: Street Address
Site plan T05CM06345 (First Review)
T13S, R13E, Section 36

RESUBMITTAL REQUIRED: Site Plan

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. If applicable, show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
3. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
4. If applicable, all easement of record must be graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
5. Please provide spot grades to ensure positive drainage, and clearly demonstrate that no nuisance ponding will occur on-site or on adjacent sites do to this proposed project.
6. Provide the Basis of Bearing for this project along Estrella Avenue.
7. Provide Bench Mark information based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
8. The plans do not meet D.S. 6-01.4.1.I which states that "Containers are to be placed so that the collection vehicle does not have to back into moving traffic, on or off the premises." Please modify the location of the Dumpster or a Development Service Modification Request (DSMR) maybe required. Contact Solid Waste Department @ 791-5543 x1136, John Clark, for approval/guidance of curbside pickup and/or for refuse enclosure questions.
9. A permit or a private improvement agreement may be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
10. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes or call out the GB at the D/W, if applicable.
11. List the consulting engineer and the owner/developer on the plans with the pertinent information.
12. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
13. Water harvesting techniques shall be incorporated into the development by conveying rooftop drainage to designated water harvesting areas. Please address how water-harvesting techniques will be incorporated into the development. Refer to the newly adopted City of Tucson Water Harvesting Guidance Manual for design considerations.
14. Call out truncated domes onto wheel chair ramps; as per Federal ADA requirements, all wheel chair ramps shall have the Truncated Domes instead of the standard grooves, which are shown on City of Tucson Standard Detail 207. Aside from the Truncated Domes, the wheel chair ramps shall be constructed in accordance with the Standard Detail 207.


If you have any questions, I can be reached at 791-5550 x1191 Jose.Ortiz@tucsonaz.gov
Jose E. Ortiz
Civil Engineer
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
01/23/2006 ANDREW CONNOR NPPO REVIEW Denied Submit NPPO plan or Application for Exception per DS 2-15.2.0.C
01/23/2006 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Landscape borders, per LUC 3.7.2.4 is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site except for points of ingress-egress refuse storage can not be located within required landscape buffer area. "Containers are to be placed so that the collection vehicle does not have to back into moving traffic, on or off the premises" per DS 6-01.4.1.I. Relocate refuse enclosure as necessary.

2. One (1) canopy tree must be provided for every (33) linear feet of interior landscape border per LUC 3.7.2.4. Additional tree is required for landscape border to the north.

3. Note: An unpaved planting area within vehicle use area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, can be provided for canopy trees.

4. Submit NPPO plan or Application for Exception per DS 2-15.2.0.C

5. Additional comments may apply.
02/24/2006 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens FOR: David Rivera
Lead Planner Principal Planner

PROJECT:T05CM06345
2094 N. Estrella Ave
Estrella Apartments
Site Plan

Transmittal date:1st Review 2/24/06

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-02.2.1.7 The required street perimeter yard setback as per LUC Sec. 3.2.6.5.A in an established area is 20' or 11/2 the height of the proposed structure, which ever is greater. Plans indicate two different elevations, each has different wall heights towards the street perimeter. Provide only one elevation with heights of wall clearly indicated in order to determine the required setback. The indicated height (21'10") for the "standard" elevation would require a setback of 32'9". The height is not indicated for the "optional" elevation but appears to be approximately 23'6" which would require a minimum setback of 35'3". The indicated setback on the plans does not meet this requirement for either type of building elevation.

Per LUC Sec. 3.2.6.4, This project has a perimeter yard indicator of BB. When adjacent to a R2 zoning classification the required perimeter yard width is 10' or ¾ the height of the wall. The elevation plans indicate a 20' 8" tall wall on the south side of the buildings. This height will require the building to be setback 15' 6" from the south property line. Please correct on plans.

The indicated perimeter yard setback from the east property line will change based on which elevation is used. There is not a dimension provided for the height of the wall on the "optional truss roof" elevation for the end wall on sheet 9 of 14.

2. DS 2-02.2.1.8 A striped cross walk is required from the handicap access aisle to the pedestrian circulation path.

A backup spur will be required at the east end of the PAAL for the parking space located in the carport for the east dwelling unit. See DS 3-05.2.2.D & Figure 2.

3. DS 2-02.2.1.12 Striped crosswalks are required between the handicap raps located in front of the garages and carports.

Access ramps at crosswalks connecting to sidewalks must be provided. In addition Truncated Dome (early warning systems) must be added to all access ramps where transitioning from the pedestrian area to the vehicular use area or at HC access aisles transitioning to the sidewalk area.

Clearly indicate the pedestrian circulation path from the sidewalk to each individual unit.

4. DS 2-02.2.1.13 If applicable, provide the location, type, size and height of existing and proposed signage.

5. DS 2-02.2.1.20 If applicable, provide all easements of record graphically shown on the plan together with recording docket and page reference.

6. DS 2-02.2.1.25 If applicable, provide existing and proposed lighting layout and type.

7. DS 2-02.2.2 Provide the maximum and proposed lot coverage percentage.

8. Provide two sets of plans for review.

9. The location of the refuse container as indicated on the plans may not be allowed in the required landscape border. See landscape and engineering reviewers comments.

10. Depending on changes made to the plans and responses to these comments additional comments may be forth coming.


If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.
02/27/2006 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2006 GBONILL1 OUT TO CUSTOMER Completed
03/01/2006 SUE REEVES REJECT SHELF Completed