Permit Number: T05CM06321
Parcel: 13338005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06321
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2006 JIM EGAN FIRE REVIEW Approved
01/03/2006 LOREN MAKUS ENGINEERING REVIEW Approved
01/09/2006 GERRY KOZIOL WWM REVIEW Approved
12/28/2005 DAVE MANN ELECTRICAL-COMMERCIAL REVIEW Approved T05CM06321 12/20/05

1. Specify the grounding at the telephone board per NEC 800.40.
2. Show Panel TD on the plans.
3. Provide a panel schedule for Panel TD.
4. Add Panel TD to the service load calculations.
12/28/2005 ANY BUILDING-COMMERCIAL REVIEW Approved S1. ADDRESS ACCESSIBILITY.
S2. PROVIDE LETTER FROM OWNER ON FUNCTION AND NUMBER OF OCCUPANTS.
S3. SHOW USE OF BACK ROOM.
S4. SHOW RECEPTION TABLE/DESK.
S5. CLARIFY WALL NEW OR EXISTING, PROVIDE DETAILS AS NECESSARY.
12/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved