Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM06321
Parcel: 13338005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06321
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2005 HEATHER THRALL ZONING REVIEW Approved
12/20/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The governing code is the 2003 Uniform Plumbing Code with local amendments.
2. Provide indirect connections for the pumped waste from the pedicure units. Reference Section 805.0, UPC 2003.
3. If the pedicure units have a hand-held spray unit, a reduced pressure backflow preventer will be required for each water connection. Provide an indirect waste for each RPBP.
4. Show the route and termination point of the T&P relief. Coordinate the detail and the water riser diagram.
5. Clarify how many P1 fixtures are being installed.
6. The pedicure units have 2 water fixture units and 2 waste fixture units. Revise the water fixture units per Table A-2, UPC 2003.
7. Clarify the point of connection for the waste line from the pedicure units and P1 fixtures to the existing 4" waste line; above or below grade?
12/20/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Provide detail of new wall. Connection at top and bottom.
12/20/2005 ROBERT SHERRY WATER REVIEW Approved
12/20/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM06321 12/20/05

1. Specify the grounding at the telephone board per NEC 800.40.
2. Show Panel TD on the plans.
3. Provide a panel schedule for Panel TD.
4. Add Panel TD to the service load calculations.
5. Overcurrent protection is sized too large for the new WH. Reference NEC 422.11 (E) (3).
12/20/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/28/2005 JMORALE1 FIRE REVIEW Needs Review
12/28/2005 JMORALE1 WWM REVIEW Needs Review
12/28/2005 JMORALE1 ENGINEERING REVIEW Needs Review