Permit Number: T05CM06270
Parcel: 11301146W

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06270
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2005 JIM EGAN FIRE REVIEW Approved
12/16/2005 TERRY STEVENS ZONING REVIEW Approved
12/16/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
12/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide an upper terminal cleanout for the waste branch located in room 108.
2. Revise the size of the branch pipe to the urinal from 3/4" to 1" so that the water velocity is 8 fps or less.
12/19/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide code analysis that justifies seperation between tenants.
2) Provide the occupant load.
3) Clarify on site plan that it is fully accessible.
4)Door swing on toilet room 107 dangerous justify door swing in or close up exterior door.
5)Provide grab bars for ramp.
6) High low water fountain.
7) Dimension smallest opening on floor plan for the accessible path.
12/19/2005 ROBERT SHERRY WATER REVIEW Approved
12/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM06270 12/19/05

1. Electrical is calling for the replacement of existing ceiling fans. Architect is calling for new ceiling fans in the same location Sheet A-2. Please clarify. If new electrical loads are indicated, provide panel, circuit, load calculations.
2. Mechanical Sheet M-1 calls for 2 New EFs. Please provide electrical power.
12/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/21/2005 GERRY KOZIOL WWM REVIEW Approved