Permit Number: T05CM06269
Parcel: 10612017R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06269
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2005 JIM EGAN FIRE REVIEW Approved
12/16/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/16/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
12/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM06269 12/16/05

1. Show compliance with the 2003 IECC.
2. Provide a maintenance receptacle for the HVAC. Reference NEC 210.63.
3. Show clearly the WH disconnect.
4. Plot the location of the existing panel. If its new location is closer to the service, rerun the fault calculations for the new distance. If the existing panel has any breakers which are series rated, the new ones shall be as well. Specify.
5. Provide feeder overcurrent protective device rating.
6. Provide service load calculations.
7. Provide the breaker sizes for B-10 and B-12.
12/16/2005 ANY ENGINEERING REVIEW Approved
12/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/19/2005 DROBEY1 WWM REVIEW Needs Review
12/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/19/2005 ROBERT SHERRY WATER REVIEW Approved