| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/16/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/16/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/16/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM06269 12/16/05 1. Show compliance with the 2003 IECC. 2. Provide a maintenance receptacle for the HVAC. Reference NEC 210.63. 3. Show clearly the WH disconnect. 4. Plot the location of the existing panel. If its new location is closer to the service, rerun the fault calculations for the new distance. If the existing panel has any breakers which are series rated, the new ones shall be as well. Specify. 5. Provide feeder overcurrent protective device rating. 6. Provide service load calculations. 7. Provide the breaker sizes for B-10 and B-12. |