Permit Number: T05CM06258
Parcel: 131120280

Address:
6044 E 30TH ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM06258
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2006 HEATHER THRALL ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Heather Thrall Senior Planner FOR: David Rivera Principal Planner


PROJECT: T05CM06258
6044 E. 30th Street
New Office Building for Mennonite Church (CHRPA Community Home Repair Projects Office)
Site Plan Transmittal date:

1st Review January 20, 2006

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This plan was reviewed for compliance with applicable divisions of the Land Use Code (LUC), Development Standard (DS), American National Standard Institute (ANSI), and International Building Code 2003 (IBC). This plan was reviewed under site plan content/format requirements of DS 2-02.

2. The proposed project is the addition of an office to an existing church site for use of the church. Per the Zoning Administrator, this project is a secondary use to the church. Further, the proposed building and the combination of the three lots encompassing the church site shall not constitute an expansion of 25% or greater, requiring only the proposed project to be examined for code compliance.

3. Per DS 2-02. 2.1.4., please revise the location map to include the adjacent Township, Range and Section numbers and provide a scale of 3 inches to equal 1 mile for the location map drawing.

4. Per DS 2-02.2.1.6 and LUC 3.2.5.3.B, the maximum height allowed for an accessory structure in a residential zone, as is applicable to this site, is 12 feet. Height is measured from average grade to the top of the roof.

A) Please show the roof line of the building on the elevation drawing, noting the height from the roof to the average grade. Note, if the roof slants, the measurement can be taken from the average midpoint of the pitch.
B) Please correct the height limit note to read that the maximum height is 12 feet.

5. Per DS 2-02.2.1.10, please show current and future sight visibility triangles.

6. Per DS 2-02.2.18 and 11, staff acknowledges this site is not full code compliance and is legal nonconforming for the current parking configuration. For record keeping purposes, please provide dimensions for the parking and parking area access lane (PAALS).

7. Per DS 2-02.2.1.12, pedestrian and handicapped access from the church building to the proposed building is required. Please provide a sidewalk and ramps with truncated domes (early warning systems) where transitioning from pedestrian to vehicle use areas. The maximum slope for a ramp is 1 to 12. Please provide a detail of the handicapped ramps proposed.

8. Per DS 2-02.2.1.13, clarify any proposed signage and free-standing lighting.

9. Per DS 2-02.2.1.20, please provide the recording docket and page of the existing utility easement.

10. Per DS 2-02.2.2.A.1, for record keeping purposes, please provide the actual proposed Floor Area Ratio. Staff acknowledges the FAR appears less than the maximum .40 allowed.

11. The three lots shown for the project requires a lot combination and associated covenants be recorded through the Pima County Recorder's Office. Please provide the lot combination information and lot covenant documents on the resubmittal. These documents can be found on our website at www.tucsonaz.gov/dsd.

12. Should you have any questions on this review, please contact me at Heather.Thrall@tucsonaz.gov or at 791-4541x1156.


If you have any questions about this transmittal, please call (520) 791-5608.
01/20/2006 HEATHER THRALL ZONING HC SITE REVIEW Denied please see zoning comments
01/24/2006 PAUL MACHADO ENGINEERING REVIEW Denied To: David Shambach DATE: January 24, 2006
Architect 1202 E. Broadway Blvd. Tucson, Arizona 85719

SUBJECT: Shalom Mennonite Office, 6044 E 30th St.
Site plan T05CM06258 (First Review)
T14S, R14E, Section 24

RESUBMITTAL REQUIRED: Site Plan and Drainage Statement.

The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
3. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
4. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
5. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
6. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
7. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
8. Show Site plan number on all sheets per D.S. 2-02.2.1.29.
9. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. Show proposed FFE.
10. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
11. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
12. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted along with the site plan and accepted with the approval of the grading plan.
3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address on the cover sheet of the DS

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/6044 E 30th St. Site
12/16/2005 JIM EGAN FIRE REVIEW Approved
12/29/2005 ANDREW CONNOR NPPO REVIEW Denied Provide acceptable documentation, (NPPO Application for Exception http://www.tucsonaz.gov/dsd/NPPOapp.pdf ), which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C
12/29/2005 ANDREW CONNOR LANDSCAPE REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2006 GBONILL1 OUT TO CUSTOMER Completed
01/26/2006 SUE REEVES REJECT SHELF Completed