Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM06244 12/7/06

1. Please add the 25% demand factor for the AC unit as required by the calculation in NEC 550.18 (B) (3). See previous comments.
2. NEC 550.31 allows the demand factors to be used for the larger of 16,000 VA for each lot or that calculated according to 550.18. See previous comments.
3. A straight demand factor may be used, 0.22 in this case of 107 lots. (16) (0.22) (107) = 376.6 + 1.9 + 1.8 + 4.8 + 5 = 390.1 KVA, or 1626A. See previous comments.
12/07/2006 LINDA BUCZYNSKI BUILDING-COMMERCIAL REVIEW Passed