Permit Number: T05CM06244
Parcel: 10701023A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM06244
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM06244 DENIED 01/25/06

COMMENTS BELOW WERE NOTED ON PREVIOUS 2 REVIEWS. THIS DESIGN SHALL BE PERFORMED BY A REGISTERED DESIGN PROFESSIONAL.

1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. Section 8.1.4 requires a statement from a design professional to certify that existing site lighting is being modified by less than 10%.
2. Clarify which lighting fixture is to be used, the 150W or the 70W. Clarify this on the plans, not just the response letter. The cut sheets have not been modified to indicate the 150W fixture.
3. It appears from the cut sheet that a new power outlet panel is being used. This was not evident in the two previous submittals. Clarify whether this is to signify a separate service for each new light, or just a separate sub-panel. Provide electrical design, including line diagram.
4. Provide panel and circuit number for new lighting fixtures, on the plans, not just the response letter.
5. Panel load calculations imply that power is being taken from the mobile home. Note that this would violate NEC 210.25.
08/14/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review