Permit Number: T05CM06244
Parcel: 10701023A

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM06244
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM06244 DENIED 01/17/06

COMMENTS BELOW WERE NOTED ON PREVIOUS REVIEW. IT IS RECOMMENDED THAT THIS DESIGN BE PERFORMED BY A REGISTERED DESIGN PROFESSIONAL.

1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. It is necessary to read this ordinance and comply with all submittal requirements.
2. Clarify which lighting fixture is to be used, the 150W or the 70W.
3. Plot location of electrical panel on plans.
4. Provide panel and circuit number for new lighting fixtures.
5. Provide panel load calculations.
01/25/2006 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review