| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/15/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 12/15/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM06244 12/15/05 1. Demonstrate compliance with Tucson Lighting Code. 2. Provide electrical design. See the attached form. Below are a few comments. 3. Provide a detailed site plan with all new and existing equipment plotted. Show panel location. 4. Provide panel and circuit number for new electrical loads. 5. Provide panel schedules and load calculations. 6. Specify conduit and conductor size and type. |
| 12/15/2005 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved |