Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM06241
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/23/2006 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Klindt Breckenridge DATE: January 24, 2006 Architect 700 N Stone Ave. Tucson, Arizona 85705 SUBJECT: Fire Station #12, 250 S. Harrison Rd. Site plan T05CM6241, Floodplain Use Permit, T05OT03195 (First Review) T14S, R15E, Section 15 RESUBMITTAL REQUIRED: Site Plan, Floodplain Use Permit and Drainage Statement. The Site Plan (SP), Floodplain Use Permit (FUP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Site Plan: 1. Please include a response letter to the comments along with the corrected copies of the SP. 2. The site plan cannot be approved prior to the approval of the FUP. 3. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. 4. Please provide property description per D.S. 2-02.2.1.3. 5. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. 6. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12. 7. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. 8. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. 9. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19. 10. Sidewalks, curbs and wheelchair ramps are required where applicable per D.S. 3-01.3.0 and installed with "Detectable Warnings" per ADAAG. 11. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. 12. Location and orientation of existing major physical features, such as railroad tracks and drainageways per D.S. 2-02.2.1.22. 13. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. 14. Show Site plan number on all sheets per D.S. 2-02.2.1.29. 15. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. 16. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice. 17. List the consulting engineer and the owner/developer on the plans with the pertinent information. 18. Add note: "Depress all landscaped areas 6" maximum for water harvesting". Drainage Statement: 1. Please include a response letter to the comments along with the corrected copies of the DS. 2. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted along with the site plan and accepted with the approval of the grading plan. 3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2. 4. Show the project address or administration address on the cover sheet of the DS. Floodplain Use Permit: 1. Show evaluation and percentage calculations on the site plan indicating the addition is not greater then the existing building (excluding land) in cost. 2. Submit the signed copy of the evaluation memorandum for records. If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax C:/250 S. Harrison Rd. Site |
| 01/26/2006 | SREEVES1 | WWM | REVIEW | Passed | 2nd folder for WWM not needed |
| 03/01/2006 | DAVID RIVERA | ZONING | REVIEW | Denied | The building plans cannot be approved until approval of the site plan has been given by all reviewers. Zoning will re-review the building plans once the approved and stamped site plan is included with the building plans. |
| 03/02/2006 | SEPTIC APPROVAL | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/03/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 03/03/2006 | SUE REEVES | REJECT SHELF | Completed |