Permit Number - T05CM06218
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/08/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Ground fault protection requirement would apply to all receptacles in the service bay area, not just the two referenced by the arrowheads. 2. Wiring method requirement would apply to all electrical loads in the service bay area, not just the two referenced by the arrowheads. Reference NEC 511.7 (A) (1). 3. Specify the height of the conduit for the new 20A circuit, to clear up any question as to whether we need to require seals or a more stringent wiring method. 4. Specify that luminaires shall be totally enclosed. Reference NEC 511.7 (B) (1) (a). |