Permit Number: T05CM06116
Parcel: 13819037A

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T05CM06116
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: March 5, 2007
ACTIVITY NUMBER: T05CM06116
PROJECT NAME: Los Reales Branch
PROJECT ADDRESS: 369 West Valencia Road
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate


APPROVED: DRAINAGE REPORT

RESUBMITTAL REQUIRED: TWO COPIES OF THE REVISED SITE PLAN

The next review of the site plan can be an over the counter review. Please contact me to schedule a time when we can meet. When we meet open a new workflow in Permits Plus and communicate to the Customer Service Representative at the counter, that the review will be an "over the counter review." Please be aware the new site plans will need to be restamped by the Fire and Zoning review sections.

The following item must be revised on the site plan.

SITE PLAN COMMENTS

1. The revised water surface elevations (WSE) found on figure 4, in the drainage report do not match the WSE shown on the site plan. Revise the site plan to show the revised WSE found in the drainage report.
03/05/2007 ANDREW CONNOR LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/13/2007 DELMA ROBEY OUT TO CUSTOMER Completed
03/13/2007 SUE REEVES REJECT SHELF Completed