Permit Number: T05CM06116
Parcel: 13819037A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM06116
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan is required prior to building plan approval.
01/08/2007 ROBERT SHERRY WATER REVIEW Approved
01/10/2007 TERRY STEVENS ZONING REVIEW Denied 01/10/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Building Plans: T05CM06116 & T06CM02269

Comments:

1. Zoning will review and approve the building plans once the site plan has been approved. Two approved and stamped copies of the approved site plan, landscape and NNPO plans must be included with the building plans.

2. Zoning will review and approve the building plans once the structural and commercial reviewers have approved the building plans.

If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.
01/11/2007 GERRY KOZIOL WWM REVIEW Passed
01/17/2007 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/29/2006 MARTIN BROWN FIRE REVIEW Denied Please add the following automatic sprinkler criteria to the plans:
1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.
Also, please show underground fire service to new building, connection point to city water system, location of fire sprinkler riser, and location of Fire Department Connection.
Indicate new canopy will be sprinklered.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2007 DELMA ROBEY OUT TO CUSTOMER Completed
01/25/2007 SUE REEVES REJECT SHELF Completed