Permit Number: T05CM06116
Parcel: 13819037A

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM06116
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2006 MARTIN BROWN FIRE REVIEW Approved
04/21/2006 ANDREW CONNOR NPPO REVIEW Approved Exception
04/21/2006 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Provide approval documentation for landscaping within ROW. Contact Gary Wittwer @ gary.wittwer@tucsonaz.gov regarding this matter.

2. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans per DS 2-02.2.1.C. Revise the dimensions of planters on landscape plan within vehicle use area to match the site plan, include site wall locations on the landscape plan.
05/11/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: May 15, 2006
ACTIVITY NUMBER: T05CM06116
PROJECT NAME: Los Reales Branch
PROJECT ADDRESS: 369 West Valencia Road
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

SUBMITTAL REQUIRED: DRAINAGE REPORT

RESUBMITTAL REQUIRED: SITE PLAN

APPROVED: GEOTECHNICIAL REPORT (Soil's Report)

1. Indicate drainage patterns and finish grades on the site plan. Show the symbol in the legend. DS 2-02.2.1.A.16.

The above comment is from the first review. It is acknowledged that the comment has been addressed on C1 Grading and Paving. It is a requirement to have general drainage patterns shown on the site plan. It is acceptable that the information is on sheet C1, however the site plan must reference the sheet C1 for the drainage information. Add a general note to the site plan referencing sheet C1 Grading and Paving for drainage patterns and grading information.

2. Provide the recordation information (book and page) for Valencia Road. Label the road as private or public. DS 2-02.2.1.A.18.

The above comment is from the first review. In the response letter it is states this information is shown on the site plan sheet SD1. Typically this information is found adjacent to the label of the road. The information does not appear to be on the site plan. It I overlook the information? Was the information added to the plan? In the response letter for the next submittal give the location of the requested information if the book and page is not shown adjacent to the street label, "Valencia Road."

3. Show on the site plan existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. DS 2-02.2.1.A.23.

Please refer comment number 1. It is acknowledged the requested information is on the grading plan however as requested in comment number 1 please add a general note referencing the topographic information can be found on sheet C1 Grading and Paving.

4. In general note number 9 spell "plain" correctly.

5. Approximately 5' of the landscape border is located within the ROW. The landscape border is required to be located entirely on the property. If approved by the City Engineer or designee, up to five (5) feet of the required ten (10) foot width be placed within the adjacent right-of-way area. Provide written approval from the Department of Transportation with the next submittal. Revise accordingly.

DRAINAGE REPORT

1. The drainage statement provided does not contain sufficient information. Please refer to the Standards Manual for Drainage Design and Floodplain Management 2.3.1. for required report content and format and 2.3.1.6. for required basin information. The Detention/Retention Manual also provides in Chapter 5 report submittal and review requirements. Please refer to both references and resubmit the drainage report.
06/12/2006 PETER MCLAUGHLIN ZONING REVIEW Approved
06/13/2006 PETER MCLAUGHLIN ZONING HC SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2006 GBONILL1 OUT TO CUSTOMER Completed
06/20/2006 SUE REEVES REJECT SHELF Completed