Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM06114
Parcel: Unknown

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T05CM06114
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2006 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
02/24/2006 CAGUILA1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
12/19/2005 GBONILL1 ENGINEERING REVIEW Needs Review
12/19/2005 GBONILL1 WWM REVIEW Needs Review
12/19/2005 GBONILL1 ZONING REVIEW Needs Review
12/19/2005 GBONILL1 FIRE REVIEW Needs Review
12/19/2005 GBONILL1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2006 CINDY AGUILAR OUT TO CUSTOMER Completed