03/12/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM06092 PV

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes).

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" All code references to the International Residential Code shall be changed from 2003 to 2006 with appropriate paragraph references.

STRUCTURAL PLANS:

1. Provide complete roof framing plans. Provide the roof slope and structural type/size (see Structural Summary form), R301.1.

ELECTRICAL NOTES:

1. Provide the exact wording and location for the marking required by NEC 690.14 (C) (2). "Photovoltaic disconnect" at each system disconnecting means.
2. Provide the exact wording and location for the warning sign required by NEC 690.17. "Warning electric shock hazard. Do not touch terminals. Terminals on both the line and load sides may be energized in the open position."
3. Provide the exact wording and location for the marking required by NEC 690.53. "Operating current __ ADC. Operating voltage __ VDC. Maximum system voltage __ VDC. Short circuit current __ ADC." at the system disconnecting means.
4. Specify that any backfed circuit breaker shall be installed in compliance with NEC 690.64 (B) (5). Label breaker with "Breaker is backfed."