Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM06085
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06085
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2006 CAGUILA1 ENGINEERING REVIEW Needs Review
01/24/2006 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review
01/24/2006 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
01/24/2006 CAGUILA1 WWM REVIEW Needs Review
01/24/2006 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/24/2006 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
01/24/2006 CAGUILA1 WATER REVIEW Needs Review
12/08/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
12/08/2005 JIM EGAN FIRE REVIEW Approved