Permit Number: T05CM06071
Parcel: 11803401B

Address:
2150 W 33RD ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM06071
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2006 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied January 17, 2006 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T05CM06071
LP2A Job No. 2060161.003

City of Tucson
201 N. Stone Ave. 1st Floor
Tucson, AZ 85701

Re: Plan Review: Urbano Residence
Address: 2275 S. Fickett Avenue

Linhart Petersen Powers Associates (LP2A), a Bureau Veritas Company, has completed a review of the following documents on behalf of the City of Tucson:

1. Plans: Two (2) sets of plans (9 sheets, 1 through 9) with cover sheet not dated or stamped.

2. Truss Calculations: None provided.

Structural Calculations: None provided.

Energy Compliance: None provided.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

LINHART PETERSEN POWERS ASSOCIATES
A Bureau Veritas Company




Randy McCoy, Senior Plans Examiner
ICC Plans Examiner


RM:pc c:/tucson\2060161.003pc1
enclosures






Re: Stories: One
Fire Sprinklers: No
Building Area (sq. ft.): 2,275(livable)
523 (garage)
655 (covered porch)


A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).


GENERAL COMMENTS:

Please indicate all braced wall panel locations. Sheet 4. Reference IRC 602.10.

Show required holddowns, as specified on lateral design or as required for all alternate braced wall panels on the foundation plan. Sheet 2. IRC

Indicate all materials used on elevation drawings. A veneer is shown on the elevation drawings, but no description is provided. Please clarify. Sheet 5. IRC 703

Grinders and headers must be within the span limitations of IRC Table R 502.1(1) & (2). Garage header is over-spanded, living room headers are overspanded.

Indicate the size and span of headers in all bearing and non-bearing walls. Sheet 4. R602.7

Indicate the size and span of all porch beams provided. Beams must be within the span limitations of IRC Table R502.1 (1) & (2). Sheet 4. R106

ARCHITECTURAL COMMENTS:

Note and specify all rood slopes. Detail note and size all roof drains/scuppers. Sheet 4. IRC Chapter 9

Glass blocks are noted as an aluminum frame window. Please clarify. Sheet 5. IRC 106.

Specify materials for waste, water and gas pipes.





MECHANICAL, ELECTRICAL AND PLUMBING COMMENTS:

Provide drainage pipe isometric showing all drain, waste and vent piping.

Provide a 4 inch diameter moisture exhaust vent for clothes dryer. Sheet 7. IRC M1501.1

Provide combustion air for all liquid and solid fuel-burning appliances including size, type and location of openings. Sheet 7. IRC 17

Provide smoke alarms in the master bedroom and outside the master in the immediate vicinity. Sheet 8. IRC313.

Provide banding to the above ground portion of gas piping. Sheet 8. E 3509.7

Move 3-way switch that is behind garage entry door to an accessible location. Sheet 8.

All 125-volt, single phase, 15 and 20 ampere receptacles installed in bathroom shall have ground-fault circuit-interrupter protection for personnel. Sheet 8. E3802.1

All 125-volt, single phase, 15 and 20 ampere receptacles installed in garages shall have ground-fault circuit-interrupter protection for personnel. Sheet 8. E3802.2

Add a receptacle outside of master bedroom door in living room as per E3801.2.2. Sheet 8

Receptacles shall be installed so that no point along the flow line in any wall space is more that 6 feet, measured horizontally, from an outlet in that space, including any wall space 2 feet as more in width. 3801.2.1


If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980 between 8:00 A.M. to 5:00 P.M., M-F.
02/01/2006 SEPTIC APPROVAL WWM REVIEW Denied NEED PERK

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
02/02/2006 SUE REEVES REJECT SHELF Completed