Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM06012
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/18/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM06012 1/18/05 1. Note that the 2003 IECC allows 0.9 W/SF for dining, not 2.5. 2. Feeder and overcurrent protective device are too small for 185A load. Feeder is good for only 135A, and OCPD is 125A. |
| 02/08/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 02/08/2006 | CAGUILA1 | FIRE | REVIEW | Needs Review |