Permit Number: T05CM06012
Parcel: 11011176E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM06012
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
01/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM06012 1/18/05

1. Note that the 2003 IECC allows 0.9 W/SF for dining, not 2.5.
2. Feeder and overcurrent protective device are too small for 185A load. Feeder is good for only 135A, and OCPD is 125A.
02/08/2006 GERRY KOZIOL WWM REVIEW Passed
02/08/2006 CAGUILA1 FIRE REVIEW Needs Review