Permit Number: T05CM06012
Parcel: 11011176E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM06012
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE STRUCTURAL ANALYSIS TO JUSTIFY ENCLOSURE.
2) CLARIFY DETAIL 2/A2 WHAT IS BENEATH 2X4 TREATED PLATE.
3) A2 WITH OCCUPANT LOAD OVER 100 WILL NEED TO BE FIRE SPRINKLERED. 903.2.1.2 CITY OF TUCSON AMENDMENTS.
4) PLEASE POVIDE LOCATION AND ACCESSIBILITY FOR RESTROOM FACILITIES SINCE OCCUPANT LOAD IS BEING INCREASED.
12/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/05/2005 ROBERT SHERRY WATER REVIEW Approved
12/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the ventilation for the expanded dining room meets the requirements of Section 401, IMC 2003.
12/07/2005 EGRANT1 FIRE REVIEW Needs Review
12/07/2005 EGRANT1 WWM REVIEW Needs Review
12/07/2005 EGRANT1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/07/2005 EGRANT1 ZONING REVIEW Needs Review
12/07/2005 EGRANT1 ENGINEERING REVIEW Needs Review