Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM06012
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/05/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE STRUCTURAL ANALYSIS TO JUSTIFY ENCLOSURE. 2) CLARIFY DETAIL 2/A2 WHAT IS BENEATH 2X4 TREATED PLATE. 3) A2 WITH OCCUPANT LOAD OVER 100 WILL NEED TO BE FIRE SPRINKLERED. 903.2.1.2 CITY OF TUCSON AMENDMENTS. 4) PLEASE POVIDE LOCATION AND ACCESSIBILITY FOR RESTROOM FACILITIES SINCE OCCUPANT LOAD IS BEING INCREASED. |
12/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
12/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the ventilation for the expanded dining room meets the requirements of Section 401, IMC 2003. |
12/07/2005 | EGRANT1 | FIRE | REVIEW | Needs Review | |
12/07/2005 | EGRANT1 | WWM | REVIEW | Needs Review | |
12/07/2005 | EGRANT1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
12/07/2005 | EGRANT1 | ZONING | REVIEW | Needs Review | |
12/07/2005 | EGRANT1 | ENGINEERING | REVIEW | Needs Review |