Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM06009
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/05/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1)PROVIDE DIMENSIONS TO CLARIFY SQ. FOOTAGE. 2) CLARIFY WHY THIS IS NOT A H3 OCCUPANCY? |
| 12/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/05/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation of the ozone generator room per Section 3705, IFC 2003. 2. Verify the piping material from the ozone generator to the ozone ejector is compatible with the ozone. |
| 12/15/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 12/15/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 12/15/2005 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |