Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM05999
Parcel: 141015620

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05999
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2006 STANTEC 2ND PARTY REVIEW REVIEW Denied January 12, 2006


To: City of Tucson Development Services Department
201 N. Stone Avenue, First Floor
Tucson, AZ 85701
Attn: David Mann, P.E., Building Code Division

Cc: Dan Dorsey
221 E. Linden
Tucson, AZ 85705

Re: Custom Home Plan – Vastine Residence
City of Tucson No. T05CM05999
Stantec Project No. 816-30015-01 (073)




Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back-check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating the action taken.

SCOPE OF REVIEW:

The scope of this review covers residential plan review of the Architectural, Structural, Plumbing, Mechanical, Model Energy and Electrical codes. All code references are to the 2003 International Residential Code (IRC) with local amendments. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ARCHITECTURAL:

No additional comments to address.

STRUCTURAL:

No additional comments to address.

PLUMBING PLANS:

No additional comments to address.

MECHANICAL PLANS:

Provide the manufacturer’s specification sheet on the proposed heat pump unit. If this is a 3 ton heat pump the designed delivery denoted to the individual rooms exceeds the capacity of the typical unit’s fan coil range.
The applicant is still submitting a mechanical plan that denotes delivered (CFM) at almost three times above the unit’s capacity. Alterations required.

ELECTRICAL PLANS:

The presented Outdoor Lighting compliance fixtures and calculations depict several miss conceptions about the code. Please read and comply with the following;
Denote the ‘light zone’ area of this location.
When a light is under a porch, only specific types are allowed to be exempt. Provide fixture cut sheets.
The applicant has submitted fixture cut sheets with the depiction of hand drawn compliance upon the sheets submitted. The City cannot accept light fixture cut sheets with the compliance component rendered by the applicant. The selected fixture must be compliant as produced by the manufacturer for allowable use.

MODEL ENERGY CODE:

There are no comments to address.


-End of Review-

If you have any questions, please call (520) 750-7474.

Sincerely,
Stantec Consulting Inc.




Steven L. Nygren, R.A.
Senior Plans Examiner

SLN:sln
01/20/2006 JMORALE1 WWM REVIEW Needs Review