Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM05986
Parcel: 10511028B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05986
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2005 GERRY KOZIOL WWM REVIEW Passed
12/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved t05cm05986 12/21/05

1. Provide a disconnecting means for the Door Operator. Reference NEC 430 Part IX.
2. Conductor for Door Operator should be #10 if protected by a 30A CB, not #12.
12/21/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved