12/21/2005 GERRY KOZIOL WWM REVIEW Passed
12/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved t05cm05986 12/21/05

1. Provide a disconnecting means for the Door Operator. Reference NEC 430 Part IX.
2. Conductor for Door Operator should be #10 if protected by a 30A CB, not #12.
12/21/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved