Permit Number: T05CM05937
Parcel: 14121024M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05937
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2005 ROBERT SHERRY WATER REVIEW Approved
11/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/30/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE FURTHER CLARIFICATION OF TENANT SPACE. UNCLEAR IF THIS AREA EXISTED BEFORE - CLARIFY EXIT PATH FROM BUILDING ETC. IS THIS A TENANT WITHIN A TENANT?
2) PROVIDE PLAN FOR RESTROOM LOCATION AND CLARIFY IF RESTOOMS ARE ACCESSIBLE.
11/30/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/30/2005 JIM EGAN FIRE REVIEW Approved
12/01/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05937 12/1/05

1. According to Lighting Fixture Schedule, all fixtures are 120V. Powered on 277V. Please clarify.
2. Please account for continuous loading on Panel H3.
3. Account for largest motor on Panel H3A.
4. New AC on Panel H3A-1,3,5 can not be found on Electrical or Mechanical Plans.
12/08/2005 CAGUILA1 ZONING REVIEW Needs Review
12/08/2005 CAGUILA1 WWM REVIEW Needs Review
12/08/2005 CAGUILA1 ENGINEERING REVIEW Needs Review