Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05937
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/30/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/30/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE FURTHER CLARIFICATION OF TENANT SPACE. UNCLEAR IF THIS AREA EXISTED BEFORE - CLARIFY EXIT PATH FROM BUILDING ETC. IS THIS A TENANT WITHIN A TENANT? 2) PROVIDE PLAN FOR RESTROOM LOCATION AND CLARIFY IF RESTOOMS ARE ACCESSIBLE. |
| 11/30/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/30/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/01/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05937 12/1/05 1. According to Lighting Fixture Schedule, all fixtures are 120V. Powered on 277V. Please clarify. 2. Please account for continuous loading on Panel H3. 3. Account for largest motor on Panel H3A. 4. New AC on Panel H3A-1,3,5 can not be found on Electrical or Mechanical Plans. |
| 12/08/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 12/08/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 12/08/2005 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |