Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: January 7, 2006
ACTIVITY NUMBER: T05CM05931
PROJECT NAME: Glaz-Tech Industries Addition
PROJECT ADDRESS: 1762 West Grant Road
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

SUBMITTAL REQUIRED: DRAINAGE REPORT


1. All lettering and dimensions will be the equivalent of twelve point or greater in size. The purpose of this requirement is to assure that the lettering is legible when reproduced or microfilmed for record keeping purposes. The current font measures to 10 point, it must be at least 12 point or greater in size. Revise all lettering to be at least 12 point.

2. Indicate project address in the site plan. DS 2-02.2.1.A.3.

3. Four foot sidewalks are required to connect the ROW to the structures. It is not clear if there is vehicular and pedestrian access off of Huachuca Street to the site/structures. Clarify in the response letter and revise accordingly. Show the dimensions of the sidewalk and PAAL and label accordingly. DS 2-02.2.1.A.11.,12.

4. Be advised sidewalks must be physically separated from any vehicular travel lane by means of a curb, grade separation, barriers, railings, or other means. (See comment number 3) DS 2-08.4.1.

5. The minimum width of two feet must be maintained between all PAALs and any obstructions (chain link fence) or a property line. Please provide dimensions where the PAAL is adjacent to the north property line (chain link fence). Revise. DS 2-02.2.1.A.11., DS 3-05.2.2.B.3.

6. Show the drainage patterns and finish grades for the site. DS 2-02.2.1.A.16.

7. Include on the site plan estimated cut and fill quantities. If cut and fill quantities equal zero, please note on the plan. DS 2-02.2.1.A.17.

8. Indicate if Grant Road and Huachuca Street are public or private roads. Indicate the book and page for Grant Road. DS 2-02.2.1.A.18.

9. It is acknowledged that the 60 half ROW dimension has bee shown however it is not clear if it is the existing ROW, future or both existing and future. Clarify label the ROW as either existing or future or both. DS2-02.2.1.A.19.

10. Show the location of the future sidewalk for Grant Road. DS 2-02.2.1.A19.

11. Label and dimension future curb and sight visibility triangles. Face of future curb shall be located
nine (9) feet from the future property line. D.S. 2-02.2.1.A.10.

12. Because this review is a full code compliant review, current site conditions must be both up to code. Be advised that Grant Road is a Major Street and Route per the MS&R ROW Plan. New sidewalks located within the ROW along an MS&R Street are required to have 6' sidewalks along the entire length of the street frontage. It is acknowledged the existing sidewalk is four feet in width. 6' sidewalks are required along Grant Road. Revise the site plan to show 6' sidewalks along entire length of the street frontage. DS 2-02.2.1.A.19.

13. Dimension from street centerline to the existing curb and sidewalk location. DS 2-02.2.1.A.21.

14. Per the Transportation Access Management Guidelines (TAMG) for an ingress/egress to an arterial street 25' curb returns are required. Indicate 25' curb returns for the ingress/egresses to Grant Road. TMAG was adopted on March 17, 2003 by Mayor and Council.

15. Handicap curb access ramps are required to be constructed with truncated domes, per recent a Federal ADA requirement. Show a detail or add a general note to the site plan indicating all public and private handicap curb access ramps will have truncated domes.

16. Sidewalks must be flood free for up to the 10-yr. event. Add a note on the plan, "All roof down spouts on all structures must be routed under any adjacent sidewalk." DS 2-08.4.1.E.

17. Show on the site plan existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. DS 2-02.2.1.A.23.

18. Show the location of the solid waste enclosure. Demonstrate vehicle maneuverability. Be aware refuse vehicles require 36' inside radius and 50' outside radius. DS 6-01, DS 2-02.2.1.A.32.

19. This property lies within the boundaries of a "Balanced Drainage Basin," which requires a detention basin facility that ensures a reduction in the existing 2, 10 and 100 year peak discharge from the site. It is acknowledged that most of the existing site is impervious. However after reviewing an aerial photo it appears the area where the building addition is going in bare ground (pervious surface). Which means the new development is subject to detention requirements. In short a drainage report addressing a reduction in the existing 2, 10 and 100 year peak discharge from the proposed development must be submitted with the second submittal. For drainage report content requirements refer to the Standards Manual for Drainage Design and Floodplain Management 2.3.1.

20. Additional comment in subsequent reviews may be forthcoming.
12/05/2005 JIM EGAN FIRE REVIEW Denied 1. Provide verification for F-2 occupancy classification.
2. Indicate fire rating for west and north exterior walls
3. Show location of existing fire hydrants.
12/08/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. List the project address. (D.S. 2-02.2.1.A.3)

2. Under the project data, revise the existing building area to include the existing office. Correct existing building area is 9,677 S.F. (D.S. 2-03.2.1.A.6)

3. Under the project data, revise the total building area to include the existing office. Correct total building area shall be 16,637 S.F. (D.S. 2-03.2.1.A.6)

4. Provide an accessible pedestrian path from the access aisle to the building entrance. If ramps are proposed, provide a detail. (ICC/ANSI A117.1-2003)

5. Post disabled parking sign and provide a detail. (D.S. 2-02.2.1.A.8)

6. Under the project data, revise the vehicle parking calculation (including the number of vehicle parking spaces required) to be based on the correct total building area referenced in above comment three (3). (D.S. 2-02.2.1.A.8) (D.S. 2-02.2.2.A.4)

7. Under the project data block, add a note which states the bicycle parking Class type required and provided. (D.S. 2-02.2.1.A.9) (D.S. 2-02.2.2.A.4)

8. Label and dimension future curb and sight visibility triangles. Face of future curb shall be located nine (9) feet from the future property line. (D.S. 2-02.2.1.A.10)


9. Is vehicular and/or pedestrian access proposed from Huachuca Street? If so, call out on the plan and indicate the drive as one-way only. Two-way PAALs shall be 24 feet in width. In addition to the PAAL, a minimum four (4) foot wide accessible sidewalk shall be provided which connects the building to the Huachuca Street right-of-way.
If access is not proposed from Huachuca Street, clearly label as such and provided adequate barrier to prevent vehicles or pedestrian from entering or exiting in that location. (D.S. 2-02.2.1.A.11) (D.S. 2-08)

10. If applicable, provide a detail of existing and or proposed free standing signage, billboard, and outdoor lighting on the site plan. (D.S. 2-02.2.2.1.A.13)

11. Indicate the location of the refuse container. (D.S. 2-02.2.1.A.32)

12. Provide the building area expansion calculation. (D.S. 2-02.2.2.A.6)

13. Extend a five (5) foot wide pedestrian refuge area along the south end and west side of the building addition. A minimum four (4) foot wide sidewalk shall be provided within the pedestrian refuge area. (D.S. 3-05.2.2.B.1) (D.S. 2-08)


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person.
12/12/2005 DAN CASTRO ZONING HC SITE REVIEW Denied See Zoning Review comments
12/12/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Street landscape borders shall be located entirely on site, except that, if approved by the City Engineer or designee, up to five (5) feet of the required ten (10) foot width be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets per LUC 3.7.2.4.3. Provide approval documentation for landscape within right of way.

2. One canopy tree must be provided for every thirty-three (33) linear feet of the street landscape borders per LUC 3.7.2.4. Additional trees must be located within the 10' required landscape buffer.

3. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a. Additional trees are required within vehicle use area.

4. Show the location of refuse storage. Note: A 6' wall is required to screen storage area from streets per LUC 3.7.2-1.

5. Add note to plan: All disturbed areas including adjacent right of ways shall be treated with ground cover such as decomposed granite to help reduce dust pollution per LUC 3.7.2.7.

6. Include irrigation design and layout per DS 2-06.5.4.A&B

7. Submit NPPO plan or application for exception per DS 2-15.0.

8. Additional comments may apply.
12/13/2005 ANDREW CONNOR NPPO REVIEW Denied Submit NPPO plan or application for exception per DS 2-15.0.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2006 JMORALE1 OUT TO CUSTOMER Completed
01/11/2006 SUE REEVES REJECT SHELF Completed