Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM05930
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2006 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T06CM05930 3rd Review 7 /27 /06 T05CM05930 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. PLEASE PROVIDE A "SPECIAL INSPECTION" FORM IDENTIFYING THE SPECIAL INSPECTOR YOU HAVE SELECTED FOR THE USE OF EPOXIED DOWELS.INTO THE EXISTING SLAB AND FOR THE EPOXIED ANCHOR BOLTS IN DETAIL 1/6 . FLOOR PLANS: 1. THE 5/8" ANCHOR BOLT MENTIONED FOR THE "ABA66" @ THE POST TO THE EXISTING MASONRY REQUIRES 7" EMBEDMENT. SEE R403.1.6 2. INTERIOR FINISH NOTES /1 ; PLEASE AMEND THE 70" ABOVE FLOOR TO 72" ABOVE FLOOR. SEE R307.2 . 3. LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS. PROVIDE NAILING SCHEDULE. SEE R602.10 . STRUCTURAL PLANS: 1. PLEASE PROVIDE A PLATE OR SOME OTHER METHOD OF AVOIDING POINT LOADS ON THE EXISTING ROOF DECK FROM THE NEW ROOF'S OVER FRAMED RAFTERS. 2. SPECIFY LUMBER GRADE AND SPECIES. SPECIFY COMBINATION SYMBOL FOR THE GLULAMS. 3. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES AND GLULAM BEAMS. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS. 4. DETAIL GABLE END BRACING CONNECTIONS. 5. JUSTIFY THE 5.125" X 12" GLULAM AT THE EXISTING WALL OPENING. 6. THE "LU26" HANGER USED IN DETAIL 2 / 6 HAS A MAXIMUM CAPACITY OF 830# OR 1000#, DEPENDING ON WHICH NAIL IS USED. PLEASE JUSTIFY THE LU26 AND SPECIFY THE NAIL. 7. PROVIDE A STRUCTURAL ENGINEER'S ANALYSIS OF THE LAG BOLTS INTO THE END GRAIN OF THE TRUSS AS SHOWN IN DETAIL 4 / 6. SEE R802.10.4 . PLUMBING PLANS: 1. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE. 2. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. 3. PLEASE SPECIFY A WATER HEATER THAT IS APPROVED FOR OUTDOOR USE OR PROVIDE AN ENCLOSURE WITH COMBUSTION AIR SUPPLIES. MECHANICAL PLANS: 1. PROVIDE THE SIZE AND LOCATION OF THE RETURN AIR DUCT AND THE FILTER FRAME. ELECTRICAL PLANS: 1. ELECTRICAL RISER DIAGRAM / 5 ; PLEASE ILLUSTRATE THE SUB-PANEL GROUNDING CONDUCTOR TERMINATING IN THE MAIN PANEL. SEE R3507.1 . 2. PLEASE CLARIFY THE NOTE NEAR "ELECTRICAL PLAN". THE SUB-PANEL IS FED BY THE MAIN PANEL AND THE FEEDERS HAVE THEIR BREAKER IN THE MAIN PANEL. 3. CLARIFY THE LOCATION AND ACCESS TO THE SUB-PANEL. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 The plans appear to have changed completely to the point of being a new floor plan. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/31/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 07/31/2006 | SUE REEVES | REJECT SHELF | Completed |